Sunny Boy Control
- Press “ESC” to enter the main menu.
- Use the down arrow key to navigate to the “Settings” menu and press “ENTER“.
- Press “ENTER” again and enter your password.
- Use the down arrow key to navigate to the “System” menu and press “ENTER“.
- Use the down arrow key to navigate to the empty line below “Inst. Function” and press “ENTER“.
- Use the down arrow key to navigate to the “Reset Op. Data” menu item and press “ENTER“.
Sunny Data Control
- Start Sunny Data Control.
- Enter the installer password.
- Select the corresponding inverter.
- Select the “Parameter” tab.
- Select “Memory Functions”.
- Change the Channel value on the right to “Reset Op. Data”.
- Confirm the Channel value by clicking the “Set” button.
Sunny Explorer
Log into Sunny Explorer.
- Enter the installer password.
- Select the corresponding inverter.
- Select the “Device” tab.
- Click the “[Edit]” button.
- In the “Reset Operating Data” list box, select the desired operating data.
- Click the “[Save]” button.
Sunny WebBox
- Log into the Sunny WebBox.
- Enter the password.
- Select the corresponding inverter.
- Select the “Parameter” tab.
- Select “Memory Funct. > List box“.
- Select “Reset Op. Data“.
- Then confirm the setting by clicking the “[Save]” button.