Bỏ qua để tới nội dung chính

Stand-Alone Grid Systems: Nối Dây Cáp PV

Installing Cables of a Battery System

(ch) Short circuit and ground fault protected installation is required up to the fuses. You can omit battery fuses if short circuit and ground fault protected installation is provided throughout, up to the stand-alone grid inverter. When selecting cable material, ensure that this is approved for short circuit and ground fault protected installation (e.g. cable type NSGAFöu).

Also note that battery acid can corrode the cable insulation. Therefore, use acid-resistant cable material at least for cables close to the batteries, and adhere to the information of the battery manufacturer.

All work on the inverter and the cabling of the PV array must be carried out by an electrically qualified person. SMA accepts no liability for the information and solutions given in the Online Service Center. Additional information can be found in our Online Service Center’s terms and conditions of use.

Bài viết được Solar SM biên dịch từ tài liệu kỹ thuật của SMA Solar Technology AG. Nếu sự cố chưa được giải quyết, hãy gửi yêu cầu hỗ trợ kỹ thuật hoặc gọi hotline 082 747 7272.