Event numbers 61, 6101 and 6107 indicatean error in the program sequence or a faulty data record.
Error 61, 6101 or 6107 “Self-diagnosis” or “Device disturbance” is displayed, and the red LED lights up. When the error occurs, the inverter does not feed any power in.
If this event number appears after parameter changes (country data set or individual parameters), please check that the settings are correct. Reset to the original settings if necessary. Parameter changes and checks must only be performed by an electrically qualified person with the permission of the grid operator.
Otherwise, the following applies:
If the message does not lead to relevant yield losses, e.g. because it only appears for a short time during the startup or shutdown process, no further action is necessary. The cause in this case is the fluctuating PV power in the lowest limit range.
However, if the message appears repeatedly or continuously, even after a full restart , the cause and corrective action must be clarified by SMA Service.
In this case, please contact the SMA Service with the following Information: