Bỏ qua để tới nội dung chính

Ssm 24-21 Exchange

  1. Safety onsite
  2. Properly Disconnect / Isolate the Inverter
  3. Turn the Key to stop Position
  4. Gently open the door of the Connection Cabinet of the inverter
  5. Switch off auxilliary circuit breaker ( F119 )
  6. Switch off Main AC Breaker
  7. Isolate SSM from the Field
  8. Switch off the DC Load SSM breaker
  9. Open all DC String Fuses for Safety. Take out the fuses and put in safe place
  10. Check Below Cables
  11. Disconnect RS485 Data Connection Cable and Power Supply cable as shown in the Picture
  12. Take out the 4 Screws attached to the cover of the SSM Board
  13. Replace the old Board with the new one.
  14. Plug the Jumper on the lowest String Monitorning Board Unit if the SSM 24-21 is located on the last Sequence of the RS485 connection in the Pin Headed S1 to T
  15. Make a note of the serial number of the Unit Installed. This serial number is the one we have to detect on the SCSMC.
  16. Re-install all other parts that has been taken out ( e.g. Cover , DC fuses, , DC Load Breaker , Data and Power Cables as they were before. )
  17. Start Up the inverter
  18. Switch On Auxilliary Circuit Breaker ( F119 )
  19. Switch On Main AC Breaker
  20. Turn key to Start Position

Bài viết được Solar SM biên dịch từ tài liệu kỹ thuật của SMA Solar Technology AG. Nếu sự cố chưa được giải quyết, hãy gửi yêu cầu hỗ trợ kỹ thuật hoặc gọi hotline 082 747 7272.