To be able to operate a SensorBox on a SBCoP, the following steps must be carried out:
- Deactivation of the analog input for the ambient temperature
- Deactivation of the analog input for the irradiation
- Adjustment of the measurement channel for the irradiation (IntSolIrr) on the SensorBox to variable “+Gi”
- Adjustment of the measurement channel for the ambient temperature (TmpAmb C) on the SensorBox to variable “+Team”
Profil2 is designed so that the measurement values for the irradiation and temperature are applied to the analogue inputs Aln 1 and AIn 7. Profil2 is designed so that the measurement values for the irradiation and temperature are applied to the analogue inputs Aln 1 and AIn 7. These measured values are transmitted from the Sunny SensorBox as channel values. Thanks to the above-mentioned configuration, these channel values are re-assigned to the inputs.
For the plant analysis, the existing module surface must be entered in Variable 1 (+A) and the module efficiency entered in Variable 2 (etaM).